Eaton 93PM – 150 kW UPS System – 480V -3W
Rated: 150 kVA / 150 kW
Input Voltage: 480V VAC, 3 Phase, 3 Wire plus GND. 60 Hz
Input Configuration: Single Input
UPS Output: 480V VAC, 3 Phase, 3 Wire plus GND. 60 Hz
Maintenance Bypass: 3 Breaker Line and Match Maintenance Bypass
Dimensions: 37.0″ Wide x 42.0″ Deep x 74.0″ High
Weight: 1,501 lbs
The UPS System has the following characteristics:
1 – Tri-Level Inverter Double Conversion Online Topology with 97% Efficiency 1 – IGBT Rectifier with DSP control with 3% Input Current THD
1 – IGBT PWM Inverter with DSP control 1 – Lot Redundant Cooling Fans
1 – Lot Redundant Power Supplies
1 – Continuous Duty Internal Static Bypass Switch
1 – Advances Battery Management System with Temperature Compensation Charging.
1 – PXGMS Network Interface Card
1 – 7” LCD Color Touch Screen Display with Comprehensive Monitoring and Trending package. LCD including the following screens:
• Meter Screen – Voltage, Current, kW, kVA, frequency.
• Utility Statistics Screen – number of outages, etc.
• Mimic Screen – Power flow diagram
• Battery Screen – Charging & Discharging status
• Efficiency Screen – Calculate and monitor Power usage, Load Profiling and Efficiency
• Alarm Event Screen -History Logging