ASCO 7000 Series and ASCO 300 Series automatic transfer switches are both widely used in backup and critical-power systems, but they are designed around different application requirements.
The right choice is not simply a matter of deciding which series is “better.” The transfer switch needs to match the facility’s required amperage, voltage, pole configuration, transfer operation, reliability requirements and overall power-system design.
For projects evaluating ASCO equipment, understanding the intended role of each series can help narrow the available options before reviewing CI Group’s automatic transfer switch inventory.
ASCO 7000 Series vs. ASCO 300 Series at a Glance
| Consideration | ASCO 300 Series | ASCO 7000 Series |
|---|---|---|
| Manufacturer Positioning | Commercial and light-industrial applications | Mission-critical applications |
| Typical Current Range | 30–3000A | Configurations available from lower amperages through 4000A, depending on design |
| Voltage | Current product family includes field-selectable voltage configurations | Multiple low-voltage configurations; medium-voltage 7000 Series equipment is also available |
| Service Entrance | Service-entrance configurations available | Service-entrance configurations available |
| Bypass-Isolation | Selection depends on specific 300 Series configuration | Dedicated 7000 Series bypass-isolation family available |
| Application Emphasis | Commercial backup power and light-industrial systems | Data centers, healthcare, industrial and other mission-critical systems |
These are general product-family distinctions. Final ATS selection should always be based on the exact electrical and project requirements rather than the series name alone.
What Is the ASCO 300 Series?
The ASCO 300 Series is designed primarily for commercial and light-industrial backup-power applications.
The current product family includes automatic transfer switches from approximately 30 to 3000 amps and offers configurations intended to transfer loads between normal utility power and an alternate power source.
Depending on the specific model and configuration, the 300 Series can support applications such as:
- Commercial buildings
- Light-industrial facilities
- Retail and office facilities
- Small and mid-sized institutional facilities
- Generator-backed electrical systems
- Service-entrance applications
- Facility backup-power systems
Current ASCO 300 Series equipment also includes field-selectable voltage configurations, which can provide additional flexibility when matching equipment to a project’s electrical requirements.
However, amperage and voltage alone should not determine whether a 300 Series ATS fits the project.
Before selecting equipment, review the factors covered in the Automatic Transfer Switch Sizing Guide: Amperage, Voltage, Poles & Application Requirements.
What Is the ASCO 7000 Series?
The ASCO 7000 Series is positioned around mission-critical power-transfer applications where system availability, transfer operation and maintainability can be particularly important.
Depending on the specific configuration, the 7000 Series can support applications such as:
- Data centers
- Healthcare facilities
- Large industrial facilities
- Critical infrastructure
- Large commercial campuses
- UPS-supported electrical systems
- Complex emergency-power systems
- Applications requiring bypass-isolation
The 7000 Series family includes multiple transfer configurations and equipment types, including standard automatic transfer switches, service-entrance equipment, bypass-isolation systems and medium-voltage transfer equipment.
That broader range of configurations can make the 7000 Series particularly relevant when the ATS is part of a more complex critical-power architecture.
For larger facilities, transfer-switch selection may also need to be coordinated with generators, UPS systems and electrical distribution equipment. CI Group’s Data Center Power Infrastructure & Critical Equipment page provides additional information about planning these systems together.
1. Application Requirements Are the First Major Difference
One of the clearest differences between the two product families is how ASCO positions them.
The 300 Series is primarily designed around commercial and light-industrial backup-power applications.
The 7000 Series is designed around mission-critical power applications where the transfer system may be supporting loads that cannot tolerate extended interruption or where the facility has more complex reliability and maintenance requirements.
That does not mean every commercial facility should use a 300 Series switch or every data center automatically requires a 7000 Series switch.
The correct series depends on the actual electrical design, operating requirements and project specification.
2. Compare the Required Amperage
Both ASCO product families cover a substantial range of ampere ratings.
The current ASCO 300 Series product family covers approximately 30 through 3000 amps.
ASCO 7000 Series low-voltage equipment is available across a broad range of capacities, with current manufacturer documentation covering configurations through 4000 amps depending on transfer type and design.
CI Group organizes available ATS equipment by amperage so projects can begin by narrowing inventory to the required capacity:
- 0–260A Automatic Transfer Switches
- 261–800A Automatic Transfer Switches
- 801–1600A Automatic Transfer Switches
- 1601–3000A Automatic Transfer Switches
- 3001+A Automatic Transfer Switches
Amperage is only the first filter. Voltage, phase, poles, transition type and application requirements still need to be confirmed.
3. Compare Voltage and Electrical Configuration
A transfer switch must match the electrical system it serves.
Before choosing between an ASCO 300 Series and 7000 Series switch, confirm:
- System voltage
- Single-phase or three-phase operation
- Frequency
- Normal source configuration
- Emergency or alternate source configuration
- Required number of poles
- Neutral and grounding arrangement
Current ASCO 300 Series equipment includes field-selectable voltage options in portions of the product family, while the 7000 Series is available in numerous low-voltage configurations and also extends into dedicated medium-voltage applications.
When replacing an existing ATS, do not assume that a switch from the same series automatically matches the existing electrical system. The actual ratings and configuration should be verified from the equipment nameplate, project documents and electrical design.
4. Consider 3-Pole vs. 4-Pole Requirements
Both series can be encountered in electrical systems where pole and neutral configuration are important selection factors.
For a three-phase system, the project may require either a 3-pole or 4-pole transfer switch depending on how the neutral and grounding system are designed.
A 3-pole ATS generally switches the three phase conductors while leaving the neutral unswitched.
A 4-pole ATS switches the neutral along with the phase conductors.
The correct configuration can depend on:
- Generator grounding
- Utility grounding
- Separately derived system requirements
- Ground-fault protection
- Neutral current
- Project engineering requirements
This decision should be based on the electrical system rather than on whether the equipment is part of the 300 or 7000 Series.
For additional selection considerations, review CI Group’s Automatic Transfer Switch Sizing Guide.
5. Evaluate Transfer Operation Requirements
Transfer operation is another area where project requirements become important.
A basic standby-power application may require a relatively straightforward transfer between utility and generator power.
A mission-critical facility may have additional requirements involving:
- Open-transition transfer
- Delayed-transition transfer
- Closed-transition transfer
- Bypass and isolation
- Maintenance without interrupting the protected load
- More complex source-control requirements
The ASCO 7000 Series family includes equipment specifically designed around open-, delayed- and closed-transition applications, as well as dedicated bypass-isolation configurations.
When Bypass-Isolation Matters
A bypass-isolation ATS provides an alternate path that can allow the primary transfer mechanism to be isolated for testing, inspection or maintenance while maintaining power to the load.
This capability can be particularly important for facilities where taking the transfer system completely out of service for maintenance would create unacceptable operational risk.
For a more detailed explanation, see What Is a Bypass-Isolation Automatic Transfer Switch and When Is It Used?
6. Both Series Can Be Used in Service-Entrance Applications
Service-entrance capability should not be treated as a simple 300-versus-7000 distinction.
ASCO offers service-entrance configurations within both product families.
If the transfer switch will be installed at the electrical service, the project needs to determine whether service-entrance-rated equipment is required and what disconnecting, overcurrent-protection, grounding and bonding requirements apply.
For more information, see What Is a Service-Entrance-Rated Automatic Transfer Switch?
7. Consider System Criticality and Maintainability
The operational importance of the load is one of the strongest reasons a project may move toward a more mission-critical transfer-switch configuration.
Consider what would happen if the ATS:
- Failed to transfer during an outage
- Needed to be removed from service
- Required maintenance
- Developed a controller fault
- Could not be tested without interrupting the load
For a standard commercial application, those requirements may differ significantly from a data center, healthcare facility or other continuously operating critical environment.
The 7000 Series offers configurations specifically designed around these types of mission-critical requirements, including bypass-isolation systems.
However, the correct choice still depends on the actual facility design. Selecting a more complex transfer switch than the application requires can add unnecessary equipment and maintenance complexity.
8. Consider Existing Equipment When Planning a Replacement
When replacing an existing ASCO transfer switch, the goal should not be to select equipment based solely on the series name printed on the existing unit.
Record the complete equipment information, including:
- Manufacturer
- Series
- Model or catalog number
- Amperage
- Voltage
- Phase
- Number of poles
- Transition type
- Enclosure
- Service-entrance configuration
- Bypass-isolation configuration, if applicable
- Controller information
- Available fault-current requirements
The replacement project should also consider whether the facility’s load or operating requirements have changed since the existing ATS was installed.
A replacement can be an opportunity to determine whether the existing configuration still fits current and future facility requirements.
9. Maintenance Requirements Should Be Part of the Decision
Regardless of whether a facility uses an ASCO 300 Series, ASCO 7000 Series or another manufacturer’s transfer switch, the ATS needs to remain operational when an outage occurs.
Inspection and maintenance planning should consider:
- Mechanical operating condition
- Electrical connections
- Transfer mechanism operation
- Controls and sensing
- Contact condition
- Alarms or fault history
- Functional transfer testing
- Bypass-isolation operation, where applicable
For additional guidance, see Automatic Transfer Switch Maintenance: Inspection, Testing & Replacement Considerations.
For inspection frequency considerations, see How Often Should an Automatic Transfer Switch Be Inspected and Tested?
CI Group also provides Automatic Transfer Switch Service & Maintenance for existing ATS equipment.
Which ASCO Transfer Switch Series Is Right for Your Project?
The ASCO 300 Series may be appropriate when the project involves a commercial or light-industrial backup-power application and the required electrical and transfer configuration is available within that product family.
The ASCO 7000 Series may be more appropriate where the application involves mission-critical loads, more complex transfer requirements, bypass-isolation, higher-capacity configurations or other critical-power requirements.
Before selecting either series, confirm:
- Required amperage
- System voltage
- Phase
- Number of poles
- Neutral configuration
- Available fault current
- Required transition type
- Service-entrance requirements
- Bypass-isolation requirements
- Enclosure
- Installation environment
- Facility criticality
- Maintenance requirements
The Automatic Transfer Switch Sizing Guide provides a more detailed review of these selection factors.
Browse Available Automatic Transfer Switches by Amperage
Once the project’s required capacity is known, review CI Group’s available automatic transfer switch inventory by amperage:
- 0–260A Automatic Transfer Switches
- 261–800A Automatic Transfer Switches
- 801–1600A Automatic Transfer Switches
- 1601–3000A Automatic Transfer Switches
- 3001+A Automatic Transfer Switches
Available equipment varies by manufacturer, series, amperage, voltage, pole configuration, transfer type, enclosure, condition and other specifications.
Related Automatic Transfer Switch Resources
Automatic Transfer Switch Sizing Guide: Amperage, Voltage, Poles & Application Requirements
Review the electrical and application requirements that should be established before selecting ATS equipment.
Automatic Transfer Switch Maintenance: Inspection, Testing & Replacement Considerations
Learn what should be evaluated when maintaining an existing ATS and when replacement may need to be considered.
What Is a Bypass-Isolation Automatic Transfer Switch and When Is It Used?
Learn how bypass-isolation equipment supports ATS maintenance and critical-power applications.
What Is a Service-Entrance-Rated Automatic Transfer Switch?
Understand when service-entrance requirements can affect transfer-switch selection.
How Often Should an Automatic Transfer Switch Be Inspected and Tested?
Review factors that influence transfer-switch inspection and testing schedules.
Need Help Identifying ASCO ATS Equipment?
Choosing between an ASCO 300 Series and ASCO 7000 Series transfer switch begins with the electrical and operational requirements of the project.
CI Group can help identify available automatic transfer switch equipment based on established amperage, voltage, pole configuration, transfer type, service-entrance requirements and other project specifications.
Browse Automatic Transfer Switch Inventory
For an existing ATS that requires inspection, testing, repair or preventative maintenance, visit Automatic Transfer Switch Service & Maintenance.